Permit Number: T12CM08060
Parcel: 129020510

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T12CM08060
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/03/2013 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. A restaurant (A2) with an occupancy load of less than 50 shall be classified as a (B) business as per the 2006 IBC, Section 303.1, Exception 1. Please change the building classification on your code summary to "B".
2. Please provide structural details and calculations for the following:
a. The new roof top mounted HVAC unit.
b. The new type II exhaust hood.
END OF REVIEW
01/09/2013 ROBERT SHERRY WATER REVIEW Approved
01/09/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
01/11/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Clarify the tags for the existing and the new rooftop A/C units: in detail 02/M1.0, both are labeled as AC-1; on sheet M3.0, the new unit is shown as both AC-1 and as AC-2.
2. Verify that a separation of at least ten feet exists between the air intake opening for the new "AC-1" and the exhaust opening for EF-1. Reference: 401.4.1, IMC 2006.
3. Verify that the amount of outside air introduced into the building is not significantly less than the amount of air being exhausted from the building (i.e. will both A/C units be interlocked with the Type II hood). Reference: Section 403.1, IMC 2006.
01/18/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
01/29/2013 GERRY KOZIOL WWM REVIEW Approved
12/27/2012 KEN BROUILLETTE FIRE REVIEW Reqs Change Please refer to 2006 IBC 303.1 Exception 1.
This should be a Group B Occupancy

Final Status

Task End Date Reviewer's Name Type of Review Description
02/07/2013 FERNE RODRIGUEZ OUT TO CUSTOMER Completed
02/07/2013 CPIERCE1 REJECT SHELF Completed