Permit Number: T12CM08053
Parcel: 10709092A

Address:
515 W KELSO ST

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T12CM08053
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/03/2013 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET D1.2; DEMOLITION NOTES: ON THE REFLECTED CEILING PLAN, DEMOLITION NOTES 9 AND 23 ARE INDICATED, BUT THOSE NOTES ARE NOT LISTED OR IDENTIFIED. VERIFY.
2. SHEET A8.1; ELEVATION 3: DO THE COUNTERS IN THE WORKROOM MEET THE ACCESSIBLE HEIGHT REQUIREMENTS LISTED IN THE IBC SECTION 1109.11? VERIFY.
3. SHEET A10.1; DETAIL 2: UPDATE NOTE 7.
4. SHEET A10.1; DETAILS 16, 17, 18, AND 19: REMOVE ALL ADAAG REFERENCES AND UPDATE THE IBC REFERENCES.
5. SHEET S1.1 (FOUNDATION PLAN); SHEET S4.1 (DETAIL 5B): PROVIDE A DIMENSION ON THE DETAIL FOR THE NEW CONCRETE LEDGE UNDER THE EXISTING SLAB, OR REFERENCE A DETAIL ON SHEET S3.1.
6. SHEET S4.1; DETAIL 1: PROVIDE THE BLOCKING INFORMATION (AT EXISTING JOISTS), INCLUDING SIZE AND CONNECTION TO THE JOISTS.
7. SHEET S4.1; DETAIL 4A: THE BEAM WIDTH DIMENSION AT THE BOTTOM OF THE STEEL PLATE SADDLE INDICATES 'BEAM WIDTH + 7/8" '. THE DIMENSION OF THE INSIDE STEEL PLATE SADDLE WIDTH INDICATES 'BEAM WIDTH + 1/8" '. SINCE THE PLATES ARE 1/2" MATERIAL, THE BOTTOM DIMENSION SHOULD BE BEAM WIDTH + 1/8" + 1/2" + 1/2" = BEAM WIDTH + 1 1/8". VERIFY.
8. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.

Final Status

Task End Date Reviewer's Name Type of Review Description
01/08/2013 CPIERCE1 REJECT SHELF Completed