Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 4TH
Permit Number - T12CM07985
Review Name: REVISION - - 4TH
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/08/2014 | FRODRIG2 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 12/19/2013 | KEN VAN KARSEN | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 12/19/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | 1. Show how the water temperature for the lavatory will be limited to a maximum of 110 degrees Fahrenheit. Reference: Section 413.1, UPC 2006 and Section 504.3, IECC 2006. 2. Provide information to show that the shower control valve conforms to the requirements of ASSE 1016. Reference: Section 418.0, UPC 2006. |
| 12/19/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | Both the restroom exhaust fan and the dryer vent shall terminate to the outside of the building. Reference: Sections 501.2 and 504.4, IMC 2006. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/08/2014 | FERNE RODRIGUEZ | OUT TO CUSTOMER | Completed |