Permit Number: T12CM07967
Parcel: 10408095C

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T12CM07967
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/19/2013 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
08/21/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide documentation of the U-factors used for the exterior walls and roof that are labeled as "other" in the list of building components (see footnote b of Part 3 of the Envelope Compliance Certificate. [Initial comment: Provide energy code compliance calculations for the building envelope; use the climate zone for Pima County < 4,000 feet. Provide sufficient detail on the drawings to evaluate the energy compliance of the building envelope. The information on the drawing shall, as a minimum, include U-factors of the envelope systems and fenestration components, along with the R-values of the insulation and the SHGC for the fenestration. Reference: Sections 101.4 and 104.2, International Energy Conservation Code 2006.]
08/21/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
08/21/2013 ROBERT SHERRY WATER REVIEW Approved
08/27/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T12CM07967
700 W Wetmore #03
Display Bldg

1. Sheet ESL101, Outdoor Lighting Calculation, indicate which Option is being used, calculation states 250,000 lum X 7.126 acres, however using 300,000 lum X 7.126 acres ?
2. Same sheet as above, indicate locations and fixtures to be used as Security Lighting and which for Special Use lighting.
Security Lighting is under lumen count, minimum 3500K color rated temperature for each lamp and fixture, not under curfew,
Special Use lighting, not under lumen count, not limited by 3500K color rated temperature , under curfew.
3. Sheet EP701, last review of 1/18/2013 did not have the delta 1 items, have these been changed and now new equipment installed ? Some of the sizes of switch gear have changed such as main breaker sizes, fault current values of switch gear and feeder sizes. Is some equipment existing as shown by dashed lines if so how can values such ampacity, fault current levels and mains be changed without changing the units ? The previous total load was 1346 KVA now 1690 KVA ? This current plan does not include a feeder schedule in order to check changes and upgrades.
How do new fault current values come into play, provide a fault current calculation for new values.
Part of the problem is that some of this information can be on other permits being applied for at same time, do not check other plans at same time, do not have access to them at same time.
Appears I need to review Delta 1 and 2, do not know what is new from Delta 1. Please indicate on plan.

Ray T Majuta
Elect Plan Review
PDSD, C of Tucson
8/28/2013
Ray.Majuta@tucsonaz.gov
520/837/4988
09/05/2013 STEVE SHIELDS ZONING REVIEW Denied PDSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: Precision Toyota of Tucson
T12CM07960, T12CM07961, T12CM07967 & T12CM07970
Building Plan (1st Review)

TRANSMITTAL DATE: September 5, 2013

1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. Zoning has reviewed the building plan for compliance with the development package and it appears that the building plan complies. But due to the amount of comments by other PDSD review agencies Zoning will not approve at this time

3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved development package. Additional comments may be forthcoming.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956

Final Status

Task End Date Reviewer's Name Type of Review Description
09/13/2013 SHANAE POWELL OUT TO CUSTOMER Completed
09/13/2013 CPIERCE1 REJECT SHELF Completed