Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - NEW
Permit Number - T12CM07967
Review Name: COMMERCIAL - NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/08/2013 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | GENERAL 1. Please provide certification of special inspectors for approval. 2. Please provide structural calculations for the following: a. All roof top mounted HVAC equipment. b. All suspended HVAC equipment c. Electrical light pole foundations. d. Flag pole foundations e. Wall hung water heaters including wall analysis 3. In order to fairly and properly assess permit and impact fees, an accurate square footage analysis is required listing all the enclosed conditioned occupied space, the exterior canopy and parking shade. 4. Building Demolition is to be under a separate permit. 5. Where are the drawings and calculations for the covered carport? SHEET AR101 6. Please provide casework elevations for all casework indicated "By Others" showing accessibility requirements. SHEET AR201 7. Detail 1: Is the fascia of the outdoor canopy stucco? Please note reference such as ST-1. END OF REVIEW |
| 01/08/2013 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Completed | |
| 01/15/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Clarify the basis for the water fixture unit and the water demand calculations; the data doesn't correspond to the referenced IPC tables and code sections. 2. Show the location and number of the proposed hose bibbs. Reference: Section 106.3.1, IPC 2006. 3. Provide tempered water for the lavatories using approved devices conforming to ASSE 1070. Reference: Section 416.5, IPC 2006. 4. Provide pressure-absorbing devices for the water connections to appliances equipped with quick-acting or solenoid valves (e.g. flush valves). Reference: Section 604.9, IPC 2006. 5. Provide a cleanout at the junction of the building drain and the building sewer. Reference: Section 708.3.5, IPC 2006. 6. Provide roof drainage calculations and plans (noted by keynote #3 on sheet AR102). Reference: Sections 1101, 1106 and 1107, IPC 2006. |
| 01/15/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide energy code compliance calculations for the building envelope; use the climate zone for Pima County < 4,000 feet. Provide sufficient detail on the drawings to evaluate the energy compliance of the building envelope. The information on the drawing shall, as a minimum, include U-factors of the envelope systems and fenestration components, along with the R-values of the insulation and the SHGC for the fenestration. Reference: Sections 101.4 and 104.2, International Energy Conservation Code 2006. 2. Provide structural details to show how the fan coil unit is to be connected to the building structure. Reference: Section 302.1, IMC 2006. 3. Revise the sequence of operation for the restroom exhaust fans so that all of the air supplied to the restrooms will be exhausted (e.g. supply air introduced into the restroom when unoccupied shall be exhausted). Reference: Section 403.2.1 (4), IMC 2006. 4. The area above the hung ceiling appears to be a return air plenum; positively pressurized exhaust ducts may not pass through a plenum. Reference: Section 601.4, IMC 2006. 5. Duct smoke detectors shall be connected to the building fire alarm system. Reference: Section 606.4.1, IMC 2006. |
| 01/15/2013 | ROBERT SHERRY | WATER | REVIEW | Denied | Verify the water demand that will be seen by the proposed 2" water meter. Tucson Water limits 2" meters to a maximum flow of 120 GPM, not the 127 GPM presented in the water calculations. |
| 01/18/2013 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T12CM07967 700 W Wetmore Precision Toyota Phase 3 1. Provide panel schedules showing loads and locations for all power, lighting and HVAC circuits on this plan. 2. Provide a continuing calculation for the site lighting conforming with the City of Tucson Outdoor Lighting Code. Other phases are being reviewed sperately from other phases, if information pertaining to this phase in other drawings, they should also be included with this set. Ray T Majuta Electrical Plan Review PDSD, City of Tucson 1/18/13 Ray.Majuta@tucsonaz.gov |
| 01/30/2013 | CHAD AMATEAU | WWM | REVIEW | Reqs Change | 1: NEED TO SUBMIT DP FOR PCRWRD APPROVAL - CHAD AMATEAU- 740-6547 2: NEED CAPACITY REVIEW - KURT STEMM - 740-6607 3: NEED PCRWRD/TWC REVIEW OF SAND & OIL INTERCEPTORS 4: NEED PCRWRD/IWC REVIEW OF LIFT STATION - 3035 W EL CAMINO DEL CERRO 5: NEED DEQ REVIEW OF THE ON-SITE PVT SEWER WITH LIFT STATION 6: NEED TO SHOW THE SIZES, LOCATION AND SERIAL NUMBER OF ALL EXISTING WATER METERS ON THE PROPERTY TO REMAIN, WITH DATES OF INSTALLATION. NEED TO SHOW THE SIZE, LOCATION AND SERIAL NUMBER OF ALL WATER METERS. NEED TO INDICATE THE SIZE AND LOCATION OF ALL PROPOSED WATER METERS, PER SEWER CONNNECTION FEE CALCULATION. |
| 12/21/2012 | RONALD BROWN | ADA | REVIEW | Passed | |
| 12/26/2012 | STEVE SHIELDS | ZONING | REVIEW | Denied | PDSD TRANSMITTAL FROM: Steve Shields Lead Planner PROJECT: Precision Toyota of Tucson T12CM07961, T12CM07969, T12CM07970, T12CM07960 & T12CM07967 Building Plan (1st Review) TRANSMITTAL DATE: December 26, 2012 1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed. 2. Zoning can not approve the building plan until a development package has been approved. 3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved development package. Additional comments may be forthcoming. If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956 |
| 12/26/2012 | KEN BROUILLETTE | FIRE | REVIEW | Approved | |
| 12/27/2012 | LOREN MAKUS | ENGINEERING | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/22/2013 | CPIERCE1 | OUT TO CUSTOMER | Completed |