Permit Number: T12CM07961
Parcel: 10408095C

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T12CM07961
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/29/2014 MARTIN BROWN FIRE REVIEW Approved
02/05/2014 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
02/06/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied The specified backflow prevention device, Watts model LF289 spill-resistant atmospheric vacuum breaker does not conform to ASSE 1001 except in the 3/8" and ½" sizes, in addition, it is not to be installed with shutoff valves located downstream of its location. Spill-resistant pressure vacuum breaker assemblies conforming to ASSE 1056 may be installed with shutoff valves located downstream. Reference: Sections 303.2, 608.13.6, and 608.13.8, IPC 2012.
02/06/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
02/19/2014 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Completed

Final Status

Task End Date Reviewer's Name Type of Review Description
02/24/2014 CPIERCE1 OUT TO CUSTOMER Completed