Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T12CM07961
Review Name: REVISION - - 1ST
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/29/2014 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 02/05/2014 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 02/06/2014 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | The specified backflow prevention device, Watts model LF289 spill-resistant atmospheric vacuum breaker does not conform to ASSE 1001 except in the 3/8" and ½" sizes, in addition, it is not to be installed with shutoff valves located downstream of its location. Spill-resistant pressure vacuum breaker assemblies conforming to ASSE 1056 may be installed with shutoff valves located downstream. Reference: Sections 303.2, 608.13.6, and 608.13.8, IPC 2012. |
| 02/06/2014 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 02/19/2014 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Completed |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/24/2014 | CPIERCE1 | OUT TO CUSTOMER | Completed |