Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T12CM07961
Parcel: 10408095C

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T12CM07961
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/19/2013 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. PREVIOUS COMMENT 11; SHEET SB001; NOTE 19 (GENERAL): CHANGE THE NOTE TO INDICATE AN ALLOWABLE BEARING PRESSURE OF 2500 PSF AT 2'-0" BELOW FINISHED GRADE ELEVATION (TO MATCH SOILS REPORT).
2. PREVIOUS COMMENT 17; SHEET SB103; KEYNOTES: NOTE 11 WAS NOT LOCATED ON THE PLAN. VERIFY.
3. PREVIOUS COMMENT 20; SHEET SF107; KEYNOTES: NOTE 9 WAS NOT LOCATED ON THE PLAN. VERIFY.
4. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
08/21/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide documentation of the U-factors used for the exterior walls and roof that are labeled as "other" in the list of building components (see footnote b of Part 3 of the Envelope Compliance Certificate. [Initial comment: Provide energy code compliance calculations for the building envelope; use the climate zone for Pima County < 4,000 feet. Provide sufficient detail on the drawings to evaluate the energy compliance of the building envelope. The information shall, as a minimum, include U-factors of the envelope systems and fenestration components, along with the R-values of the insulation and the SHGC for the fenestration. Reference: Sections 101.4 and 104.2, International Energy Conservation Code 2006.]
2. The source-capture exhaust system is an integral component of the automotive service bays. The mechanical plans cannot be approved unless a design for the source-capture exhaust system is included with the drawing set or the request for a deferred submittal has been approved by the building official. [Initial comment: Provide a design for the source-capture exhaust system for operating motor vehicles or submit a request to the building official for a deferred submittal. Reference: Section 502.14, IMC 2006.]
08/21/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T12CM07961
700 W Wetmore Rd #01
Fixed OPS Bldg.

1.Sheet ESC101A, Outdoor Lighting Calculations are incorrect. Using Option 2 in the E3 area allows 250,000 lumens of Full Cut of Lighting, you show that 250,000 lumens is to be used however you use 300,000 to multiply the 7.126 acres for 2,137,800 Lumens when it should be 1,781,500 L.
Do not understand what is meant by allowable installed lumens ?
The asterisk which should signify "lamp used for Security
Night Lighting" does not show up on plans as to where Security Night Lighting is located ? Indicate on plan which lights to be used as Security.
Chapter 7 of Outdoor Lighting Code 701.3 -special use lighting exempt from lumen count and source color temperature restrictions , curfew restrictions apply.
Security lighting for special use areas, has to comply with 701.5-- comply with lumen count and color rated
temperature minimum 3500K for source. These items to be distinctly shown on plan.
The fixture specification sheets do not identify color rated temperature ? The Fixture Schedule on plan indicated T1 thur T4 as KAE3, the spec sheet shows as KSF2 ?
Are receptacles shown on sheet EP102 to be GFCI protected per 511.12 of NEC ? Could not find in notes.

Ray T Majuta
Elect Plan Review
PDSD, C of Tuc
8/22/2013
Ray.Majuta@tucsonaz.gov
520/837/4988
08/21/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Venting for a sand/oil separator is intended to protect the separator from pressure fluctuations that could cause the separator to become air-bound, be subjected to siphoning, or accumulate flammable vapors. Provide venting per the manufacturer's recommendations. All vents shall drain back to the separator. Reference: Sections 905.2 and 1003.2, IPC 2006. [Initial comment: Provide a vent for the sand/oil interceptor. Reference: Section 1003.9, IPC 2006.]
09/05/2013 STEVE SHIELDS ZONING REVIEW Denied PDSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: Precision Toyota of Tucson
T12CM07960, T12CM07961, T12CM07967 & T12CM07970
Building Plan (1st Review)

TRANSMITTAL DATE: September 5, 2013

1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. Zoning has reviewed the building plan for compliance with the development package and it appears that the building plan complies. But due to the amount of comments by other PDSD review agencies Zoning will not approve at this time

3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved development package. Additional comments may be forthcoming.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956

Final Status

Task End Date Reviewer's Name Type of Review Description
09/13/2013 SHANAE POWELL OUT TO CUSTOMER Completed
09/13/2013 CPIERCE1 REJECT SHELF Completed