Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T12CM07949
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
03/15/2013 | TERRY STEVENS | ZONING | REVIEW | Denied | Provide a copy of the approved site plan. Provide dimensions to the top of walls and top of parapets in order to verify the required setbacks. This can be reviewed and approved over the counter by setting an appointment with me. Terry Stevens @ 837-4961. |
03/20/2013 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approv-Cond | Item 1: Please reference Zoning comments to this request. Item 2. As per details on the structural drawings, field welding, structural masonry and bolts in concrete are shown which are all items of construction listed requiring special spections in the 2012 IBC, Section 1705. If you require no special inspections please provide a written statement that no special inspections are required. END OF REVIEW |
03/22/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | [Original comment: Provide riser diagrams for all DWV, water and gas piping.] 1. Coordinate the fixtures called out on S & V Riser Diagram 3/P2.1 with the fixtures shown on the plumbing floor plans. Reference: Section 107.2.1, IBC 2012. 2. The minimum outlet size for a floor drain in a common laundry room is 3-inches in diameter. Reference: Section 412.4, IPC 2012. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
03/29/2013 | SHANAE POWELL | OUT TO CUSTOMER | Completed |