Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - NEW
Permit Number - T12CM07949
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/02/2013 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | GENERAL 1. Please provide approved site plan 2. Please confirm the special inspections required and provide certification of the special inspectors selected. 3. The following doors are not compliant with the 2006 IBC, Section 1005.2 because in their open position they reduce the means of egress by more than 1/2 the width: 161A, 265A and 365A. Please revise and resubmit. SHEET A1.0 3. Add total number of occupants to Code Check List SHEET A2.1 4. Please call out and detail reference the 8' high masonry fence at the patio. 5. Provide a 5' turn around in the laundry room. SHEETS A2.1, A2.2 AND A2.3 6. Please confirm the exterior stair requirements as to the 2006 IBC, Section 1023 concerning minimum area opening requirements and open side location. SHEET S3.0 7. Page 29 of the calculations calls for 2x12s @ 16"o.c. whereas the drawings show FJ3, 2x10s @16"o.c. Please reconcile. 8. Page 32 of the calculations calls for 2-2x12s whereas the drawings show 2-2x8s. Please reconcile. SHEET S3.1 9. Page 29 of the calculations calls for 2x12s @ 16"o.c. whereas the drawings show FJ3, 2x10s @16"o.c. Please reconcile. 10. Page 32 of the calculations calls for 2-2x12s whereas the drawings show 2-2x8s. Please reconcile. 11. Page 8 of the calculations calls for 3-2x8s whereas the drawings show 3-2x6s. Please reconcile. 12. Please provide structural calculations for all roof mounted HVAC equipment. END OF REVIEW |
01/02/2013 | GERRY KOZIOL | WWM | REVIEW | Denied | 1: GROUP DWELLING - DP12-0209 2: NEED DP REVIEW & APPROVAL - PCRWRD/CHAD AMATEAU - 740-6547 - CONNECTING TO 1-1/2 " WATER METER PER DRAWING P1.1 AND CONNECTING TO 6" PUBLIC SEWER IN CHERRY AV WITH A 4" HCS 3: NEED CAPACITY REVIEW - PCRWRD/KURT STEMM 740-6534 4: NEED PCRWRD/INDUSTRIAL WASTEWATER CONTROL (IWC) REVIEW OF KITCHEN / 750 GALLON GREASE INTERCEPTOR - FT "RUSTY" RICCABONI, JR. - 724-6200 - 3035 W EL CAMINO DEL CERRO |
01/03/2013 | KEN BROUILLETTE | FIRE | REVIEW | Approv-Cond | The entry gates shall have rapid entry capabilities per the IFC and local amendments and standards. |
01/03/2013 | ROBERT SHERRY | WATER | REVIEW | Approved | |
01/04/2013 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
01/04/2013 | LEERAY HANLY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1) PP P1.1 These plans are per IPC, indicate grease interceptor is sized per IPC tables. 2) Show required antisiphon devices for water heaters . IPC 504.1 3) Provide riser diagrams for all DWV, water and gas piping. 4) Coordinate referenced details; there are references to a page P2.1 which are incorrect and references to a page P2.2 which is not included in this plan set. |
01/04/2013 | LEERAY HANLY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
12/19/2012 | TERRY STEVENS | ZONING | REVIEW | Denied | Zoning cannot approve the building plan until the development package has been approved. |
12/20/2012 | JASON GREEN | ENGINEERING | REVIEW | Approved | ENG will stamp the building plan approved upon approval of the DP Package, DP12-0209. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
03/13/2013 | CPIERCE1 | REJECT SHELF | Completed |