Permit Number: T12CM07930
Parcel: 99999999A

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T12CM07930
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/17/2012 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. GENERAL: SEALED, SIGNED, AND DATED STRUCTURAL CALCULATIONS FOR THE TWO LIGHT POLE FOUNDATIONS ARE REQUIRED.
12/17/2012 STEVE SHIELDS ZONING REVIEW Approved
12/17/2012 JASON GREEN ENGINEERING REVIEW Approved
12/17/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T12CM07930
1500 E Tucson market PL
Site Lighting

1. All submitted plans are required to be minimum 3/32" text size for numbering, lettering upper and lower case. The spec's sheets for lighting on sheet E-6 do not qualify.
2. How did the amount for Phase 3 Lumens ( 1,733,771) get figured ?

Ray T Majuta
Elect Plan Review
DPDS, C of Tuc
12/17/2012
Ray,Majuta@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
01/17/2013 SHANAE POWELL OUT TO CUSTOMER Completed