Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T12CM07930
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/17/2012 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. GENERAL: SEALED, SIGNED, AND DATED STRUCTURAL CALCULATIONS FOR THE TWO LIGHT POLE FOUNDATIONS ARE REQUIRED. |
| 12/17/2012 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 12/17/2012 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
| 12/17/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T12CM07930 1500 E Tucson market PL Site Lighting 1. All submitted plans are required to be minimum 3/32" text size for numbering, lettering upper and lower case. The spec's sheets for lighting on sheet E-6 do not qualify. 2. How did the amount for Phase 3 Lumens ( 1,733,771) get figured ? Ray T Majuta Elect Plan Review DPDS, C of Tuc 12/17/2012 Ray,Majuta@tucsonaz.gov |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/17/2013 | SHANAE POWELL | OUT TO CUSTOMER | Completed |