Permit Number: T12CM07916
Parcel: 14026045A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T12CM07916
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/15/2013 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. GENERAL: ALL NEW DETAILS/NOTES PROVIDED ON 8 1/2" X 11" SHEETS MUST BE PLACED ON THE FULL SIZED DRAWINGS. INCLUDED ARE SECTION 2, PLAN 4, SECTION 5, AND GENERAL STRUCTURAL NOTES. 2. SHEET P-2: REMOVE THE WATER HEATER SUPPORT DETAIL AND REPLACE IT WITH THE NEW DETAIL.
3. SECTION 5 (NEW 8 1/2" X 11"): PROVIDE INFORMATION ON THIS SECTION, INCLUDING PLYWOOD THICKNESS AT THE PLATFORM, THE STEEL PLATE SIZE AND CONNECTION TO THE WALL STUDS, THE STEEL ANGLE BRACE SIZE, AND THE WELDED CONNECTION OF THE ANGLES TO THE STEEL PLATE.
4. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
01/15/2013 ROBERT SHERRY WATER REVIEW Approved
01/15/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
01/15/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
01/23/2013 SPOWELL1 WWM REVIEW Needs Review