Permit Number: T12CM07916
Parcel: 14026045A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T12CM07916
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/15/2013 CPIERCE1 WWM REVIEW Needs Review
12/14/2012 TERRY STEVENS ZONING REVIEW Approved
12/14/2012 LOREN MAKUS ENGINEERING REVIEW Approved
12/14/2012 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
12/14/2012 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET IA1.0; KEYNOTE 11: A NOTE WILL BE ADDED TO THE PROJECT AT THIS TIME THAT THE NEW PIT LEVELERS ARE NOT INCLUDED IN THIS PERMIT. ADDITION OF THE LEVELERS AT A LATER DATE WILL REQUIRE A PERMIT REVISION AND A CHANGE IN PERMIT FEES.
2. SHEET IA1.1; PLAN: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32' IN HEIGHT. REVISE THE ELEVATION INDICATORS.
3. SHEET IA4.0; ELEVATION 1(B): PROVIDE A DIMENSION FROM THE BACK WALL TO THE VERTICAL GRAB BAR.
4. SHEET IA4.0; ELEVATION 1(B): PROVIDE A DIMENSION TO THE PAPER DISPENSER.
5. SHEET IA4.0; ELEVATION 1(A): PROVIDE A DIMENSION FROM THE SIDE WALL TO THE HORIZONTAL GRAB BAR.
6. SHEET IA4.0; RESTROOM LEGEND: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32' IN HEIGHT.
7. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
12/14/2012 ERIC NEWCOMB ADA REVIEW Passed
12/17/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide structural calculations to verify that the existing roof is capable of supporting the additional dead load due to the installation of the roof top unit. Reference: Section 302.1, IMC 2006.
12/17/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide structural calculations to show that the existing wall can safely support the water heater . Reference: Sections 310.0 and 314.5, UPC 2006.
2. Provide a vacuum relief for the water heater. Reference: Section 608.7, UPC 2006.
3. Provide a site plan showing the location of the building, utility services (i.e. water and sewer), and the property lines.
12/17/2012 ROBERT SHERRY WATER REVIEW Denied Show the location of the water meter and the backflow preventer for this building.
12/17/2012 KEN BROUILLETTE FIRE REVIEW Approved
12/17/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved