Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL - TI ALL
Permit Number - T12CM07913
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/11/2013 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
01/14/2013 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T12CM07913 The Com Check report on Interior Lighting must be signed and sealed by the Electrical Engineer. Not signed by anyone. The Com Check report must also have an address under project title. Ray T Majuta Elect Plan Review PSDS-C of Tuc 1/14/13 Ray.Majuta@tucsonaz.gov |
01/15/2013 | MARTIN BROWN | FIRE | REVIEW | Denied | Unable to determine if architect intends to install fire sprinklers and/or an alarm system (see notes on Sheet A001) Please verify. |
01/16/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Comment not addressed. Section R4-30-304 of the Rules of the Arizona State Board of Technical Registration, states that a notation shall be placed beneath the seal, either written, typed, or electronically generated, that provides the day, month, and year of the expiration of current registration. (Effective March 8, 2008). 2. Comment not addressed. Provide the minimum plumbing facilities required by Table 2902.1, IBC 2006, for mercantile occupancy (e.g. a drinking fountain). |
01/16/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | All mechanical notes deleted from the drawings. |