Permit Number: T12CM07913
Parcel: 10605143A

Address:
3719 N ORACLE RD

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T12CM07913
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/19/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T12CM07913
3719 N Oracle Rd

1. Electrical drawings for changes were not submitted with this set of plans.

Ray T Majuta
Elect Plan Review
PDSD, C of Tucson
12/19/2012
Ray.Majuta@tucsonaz.gov
12/20/2012 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied GENERAL
1. Where are your structural, mechanical, plumbing and electrical drawings??
2. Several of your drawings have lettering sizes that are below the COT standards of 3/32" upper and lower case. Please revise all actual lettering heights to 3/32" and resubmit.
SHEET A002
3. As per the 2006 IBC, Section 1014.2.2, exiting through a store room is not allowable.
4. The occupant load is incorrect. Please recalculate and resubmit. Verify all plumbing counts and required exits to the new occupant load.
END OF REVIEW
12/28/2012 MARTIN BROWN FIRE REVIEW Denied Notes on page A001 refer to sprinkler and alarm systems. Verify existence of each or remove notes.
Occupant load on sheet A002 incorrect. Recalculate.
Insufficient exits. Can not use door in stock room as an exit.
Verify code compliant exits are 1/2 the diagonal distance from each other.
12/28/2012 GERRY KOZIOL WWM REVIEW Passed
12/31/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Section R4-30-304 of the Rules of the Arizona State Board of Technical Registration, states that a notation shall be placed beneath the seal, either written, typed, or electronically generated, that provides the day, month, and year of the expiration of current registration. (Effective March 8, 2008).
2. Provide the minimum plumbing facilities required by Table 2902.1, IBC 2006, for mercantile occupancy (e.g. a drinking fountain).
12/31/2012 ROBERT SHERRY WATER REVIEW Approved
12/31/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Section R4-30-304 of the Rules of the Arizona State Board of Technical Registration, states that a notation shall be placed beneath the seal, either written, typed, or electronically generated, that provides the day, month, and year of the expiration of current registration. (Effective March 8, 2008).
2. Note #13 of the demolition general notes calls for the existing thermostats to be removed; what will replace them? Clarify the scope of the mechanical work and provide construction documents drawn to scale and with sufficient detail and clarity to demonstrate that the work complies with the applicable codes. Reference: Section 106.3.1, IBC 2006.

Final Status

Task End Date Reviewer's Name Type of Review Description
01/02/2013 CPIERCE1 REJECT SHELF Completed