Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T12CM07913
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
12/19/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T12CM07913 3719 N Oracle Rd 1. Electrical drawings for changes were not submitted with this set of plans. Ray T Majuta Elect Plan Review PDSD, C of Tucson 12/19/2012 Ray.Majuta@tucsonaz.gov |
12/20/2012 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | GENERAL 1. Where are your structural, mechanical, plumbing and electrical drawings?? 2. Several of your drawings have lettering sizes that are below the COT standards of 3/32" upper and lower case. Please revise all actual lettering heights to 3/32" and resubmit. SHEET A002 3. As per the 2006 IBC, Section 1014.2.2, exiting through a store room is not allowable. 4. The occupant load is incorrect. Please recalculate and resubmit. Verify all plumbing counts and required exits to the new occupant load. END OF REVIEW |
12/28/2012 | GERRY KOZIOL | WWM | REVIEW | Passed | |
12/28/2012 | MARTIN BROWN | FIRE | REVIEW | Denied | Notes on page A001 refer to sprinkler and alarm systems. Verify existence of each or remove notes. Occupant load on sheet A002 incorrect. Recalculate. Insufficient exits. Can not use door in stock room as an exit. Verify code compliant exits are 1/2 the diagonal distance from each other. |
12/31/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Section R4-30-304 of the Rules of the Arizona State Board of Technical Registration, states that a notation shall be placed beneath the seal, either written, typed, or electronically generated, that provides the day, month, and year of the expiration of current registration. (Effective March 8, 2008). 2. Provide the minimum plumbing facilities required by Table 2902.1, IBC 2006, for mercantile occupancy (e.g. a drinking fountain). |
12/31/2012 | ROBERT SHERRY | WATER | REVIEW | Approved | |
12/31/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Section R4-30-304 of the Rules of the Arizona State Board of Technical Registration, states that a notation shall be placed beneath the seal, either written, typed, or electronically generated, that provides the day, month, and year of the expiration of current registration. (Effective March 8, 2008). 2. Note #13 of the demolition general notes calls for the existing thermostats to be removed; what will replace them? Clarify the scope of the mechanical work and provide construction documents drawn to scale and with sufficient detail and clarity to demonstrate that the work complies with the applicable codes. Reference: Section 106.3.1, IBC 2006. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
01/02/2013 | CPIERCE1 | REJECT SHELF | Completed |