Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T12CM07887
Parcel: 137055220

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T12CM07887
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/04/2013 CPIERCE1 WWM REVIEW Needs Review
12/13/2012 STEVE SHIELDS ZONING REVIEW Approved
12/13/2012 LAITH ALSHAMI ENGINEERING REVIEW Approved
12/14/2012 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
12/14/2012 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET A1.2; PLUMBING SCHEDULE: PROVIDE A DETAIL FOR THE HOT WATER HEATER (P3) SUPPORT.
2. SHEET A2; FIXTURE KEYED NOTES: NOTE 3 WAS NOT LOCATED ON THE PLAN. VERIFY.
3. SHEET A2; FIXTURE SCHEDULE: PROVIDE AN ELEVATION OR NOTE ON THE PERTINENT FIXTURES INDICATING IBC SECTIONS 1109.11 AND 1109.12 ARE MET FOR ACCESSIBILITY.
4. GENERAL: THE MECHANICAL, ELECTRICAL, AND PLUMBING DRAWINGS WERE NOT INCLUDED IN THIS REVIEW SET. PROVIDE.
5. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
12/14/2012 ERIC NEWCOMB ADA REVIEW Passed
12/18/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Revise the sequence of operation for the restroom exhaust fans so that all of the air supplied to the restrooms will be exhausted. Reference: Section 403.2.1 (4), IMC 2006.
12/18/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Clarify the plumbing code to be used for this activity. The pipe sizing chart on sheet P2 refers to the 2006 UPC but the appendix and chart used for pipe sizing is from the 2006 IPC. This review has been made using the 2006 UPC based on the Architect's code summary.
2. Provide a design for the mounting shelf for the water heater along with structural calculations to show that the water heater is safely supported. Reference: Section 314.5, UPC 2006.
3. Clarify how the tempered water is to be provided to the lavatories. ASSE standard 1016 is for temperature control at the hot water source while ASSE 1017 and ASSE 1070 control the temperature at the point-of-use.
12/18/2012 ROBERT SHERRY WATER REVIEW Approved
12/18/2012 KEN BROUILLETTE FIRE REVIEW Approved
12/18/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T12CM07887
1183 E Irvington

1. Show on plan location of Main SES.
2. Show the existing load on the SES and indicate how load obtained.
3. Provide the fault current at Main 200 amp Disconnect and how the 10,000 aic was obtained.

Ray T Majuta
Elect Plan Review
PDSD, C of T
12/18/2012
Ray.Majuta@tucsonaz.gov