Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T12CM07887
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/04/2013 | CPIERCE1 | WWM | REVIEW | Needs Review | |
12/13/2012 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
12/13/2012 | LAITH ALSHAMI | ENGINEERING | REVIEW | Approved | |
12/14/2012 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
12/14/2012 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET A1.2; PLUMBING SCHEDULE: PROVIDE A DETAIL FOR THE HOT WATER HEATER (P3) SUPPORT. 2. SHEET A2; FIXTURE KEYED NOTES: NOTE 3 WAS NOT LOCATED ON THE PLAN. VERIFY. 3. SHEET A2; FIXTURE SCHEDULE: PROVIDE AN ELEVATION OR NOTE ON THE PERTINENT FIXTURES INDICATING IBC SECTIONS 1109.11 AND 1109.12 ARE MET FOR ACCESSIBILITY. 4. GENERAL: THE MECHANICAL, ELECTRICAL, AND PLUMBING DRAWINGS WERE NOT INCLUDED IN THIS REVIEW SET. PROVIDE. 5. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
12/14/2012 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
12/18/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Revise the sequence of operation for the restroom exhaust fans so that all of the air supplied to the restrooms will be exhausted. Reference: Section 403.2.1 (4), IMC 2006. |
12/18/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Clarify the plumbing code to be used for this activity. The pipe sizing chart on sheet P2 refers to the 2006 UPC but the appendix and chart used for pipe sizing is from the 2006 IPC. This review has been made using the 2006 UPC based on the Architect's code summary. 2. Provide a design for the mounting shelf for the water heater along with structural calculations to show that the water heater is safely supported. Reference: Section 314.5, UPC 2006. 3. Clarify how the tempered water is to be provided to the lavatories. ASSE standard 1016 is for temperature control at the hot water source while ASSE 1017 and ASSE 1070 control the temperature at the point-of-use. |
12/18/2012 | ROBERT SHERRY | WATER | REVIEW | Approved | |
12/18/2012 | KEN BROUILLETTE | FIRE | REVIEW | Approved | |
12/18/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T12CM07887 1183 E Irvington 1. Show on plan location of Main SES. 2. Show the existing load on the SES and indicate how load obtained. 3. Provide the fault current at Main 200 amp Disconnect and how the 10,000 aic was obtained. Ray T Majuta Elect Plan Review PDSD, C of T 12/18/2012 Ray.Majuta@tucsonaz.gov |