Permit Number: T12CM07882
Parcel: 12709005A

Address:
5550 E 5TH ST

Review Status: Completed

Review Details: WALK THRU - COMM

Permit Number - T12CM07882
Review Name: WALK THRU - COMM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/14/2012 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
12/14/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Revise the CHWS and HHWS piping to comply with the requirements of Section 1206.1.1, IMC 2006. (See the piping between the two air handlers; also, check the flow arrows.)
12/14/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved