Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T12CM07876
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/11/2013 | KEN BROUILLETTE | FIRE | REVIEW | Approved | |
| 02/20/2013 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 02/25/2013 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 02/28/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. The civil sheet, 11of 18, indicates a section of the building sewer has a length of 110 feet; cleanouts shall be installed at a maximum interval of 100 feet.[Original comment: Provide cleanouts in the building sewer at intervals not exceeding 100 feet (see sheet 11 of 18). Reference: Section 708.3.2, IPC 2006.] 2. Sizing of the scuppers shall be done using the hydraulic principles of a rectangular weir (e.g. using the Francis formula) to limit the ponding on the roof. [Original comment: Provide sizing calculations for the overflow roof scuppers. Include the contributory flow from adjacent roof areas as appropriate. Reference: Sections 1106 and 1107.3, IPC 2006.] |
| 02/28/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Installation of an exhaust system requires a valid permit from the City of Tucson. If the installation of the in-ground exhaust system is to be done concurrently with the construction of this building, all of the appropriate plans (electrical, mechanical, and architectural) shall be included with the drawings for this activity. Reference: Section 106.1, IMC 2006. [Original comment: Provide a design for the source-capture exhaust system for operating motor vehicles. Reference: Section 502.14, IMC 2006.] |
| 03/10/2013 | GERRY KOZIOL | WWM | REVIEW | Denied | NEED APPROVED DP - DP12-0161 NEED IWC NEED CAPACITY NEED SIZE, LOCATION AND NUMBER OF W.M. REMOVED FOR CREDIT IF APPLICABLE. |