Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T12CM07857
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/13/2012 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 12/17/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide structural details to show how the fan coil units are to be connected to the building structure. Reference: Section 302.1, IMC 2006. 2. Revise the mechanical design as required to avoid using the corridor as a return air duct. Reference: Section 601.2, IMC 2006. |
| 12/17/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 12/17/2012 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 12/17/2012 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET g1.2; CODE ANALYSIS: UNDER THE OCCUPANCY LOAD, A NOTE INDICATES THAT 40 IS THE OCCUPANCY LOAD ALLOWED, BUT THERE WILL BE AN ACTUAL OCCUPANCY LOAD OF 72 PEOPLE. CLARIFY THE STATEMENT ON THE PLANS. |
| 12/17/2012 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
| 12/17/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 12/17/2012 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 12/17/2012 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 12/17/2012 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
| 12/24/2012 | GERRY KOZIOL | WWM | REVIEW | Approved |