Permit Number: T12CM07857
Parcel: 122184340

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T12CM07857
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/13/2012 MARTIN BROWN FIRE REVIEW Approved
12/17/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide structural details to show how the fan coil units are to be connected to the building structure. Reference: Section 302.1, IMC 2006.
2. Revise the mechanical design as required to avoid using the corridor as a return air duct. Reference: Section 601.2, IMC 2006.
12/17/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
12/17/2012 ROBERT SHERRY WATER REVIEW Approved
12/17/2012 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET g1.2; CODE ANALYSIS: UNDER THE OCCUPANCY LOAD, A NOTE INDICATES THAT 40 IS THE OCCUPANCY LOAD ALLOWED, BUT THERE WILL BE AN ACTUAL OCCUPANCY LOAD OF 72 PEOPLE. CLARIFY THE STATEMENT ON THE PLANS.
12/17/2012 JASON GREEN ENGINEERING REVIEW Approved
12/17/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
12/17/2012 STEVE SHIELDS ZONING REVIEW Approved
12/17/2012 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
12/17/2012 ERIC NEWCOMB ADA REVIEW Passed
12/24/2012 GERRY KOZIOL WWM REVIEW Approved