Review Date Reviewer's Name Type of Review Description Status Comments
12/11/2012 STEVE SHIELDS ZONING REVIEW Approved
12/11/2012 GERRY KOZIOL WWM REVIEW Approved
12/11/2012 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
12/11/2012 ERIC NEWCOMB ADA REVIEW Passed
12/12/2012 ROBERT SHERRY WATER REVIEW Denied 1. Provide the size of the existing water meter and the existing backflow assembly.
2. Compare the total water demand with the meter size.
12/12/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide a waste anf vent riser diagram.
2. Show how the hot water temperature at the lavatories will be limited to 110 degrees Fahrenheit.
3. Show how the water heater is to be supported.
12/12/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide ventilation for the new restrooms.
12/12/2012 MARTIN BROWN FIRE REVIEW Denied Note 5 on sheet A1.0 indicates "door to be deadbolted in closed position". Deadbolts not allowable by code. Verify. Please show new exiting diagram with dimensions to exits.
12/12/2012 LOREN MAKUS ENGINEERING REVIEW Approved
12/12/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
12/12/2012 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved NO COMMENTS.