Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T12CM07827
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/11/2012 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 12/11/2012 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 12/11/2012 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 12/11/2012 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
| 12/12/2012 | ROBERT SHERRY | WATER | REVIEW | Denied | 1. Provide the size of the existing water meter and the existing backflow assembly. 2. Compare the total water demand with the meter size. |
| 12/12/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide a waste anf vent riser diagram. 2. Show how the hot water temperature at the lavatories will be limited to 110 degrees Fahrenheit. 3. Show how the water heater is to be supported. |
| 12/12/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Provide ventilation for the new restrooms. |
| 12/12/2012 | MARTIN BROWN | FIRE | REVIEW | Denied | Note 5 on sheet A1.0 indicates "door to be deadbolted in closed position". Deadbolts not allowable by code. Verify. Please show new exiting diagram with dimensions to exits. |
| 12/12/2012 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 12/12/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 12/12/2012 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | NO COMMENTS. |