Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T12CM07826
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/11/2012 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET TS.1; PROJECT DATA: THE NUMBER OF EXITS LISTED FOR THE PATIO SPACE IS ONE. TABLE 1015.1 OF THE 2006 IBC STATES THAT TWO EXITS ARE REQUIRED. VERIFY. 2. SHEET A.1; GENERAL NOTES: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE. 3. SHEET A.2; GENERAL NOTES: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE. 4. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 12/11/2012 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 12/11/2012 | PAUL MACHADO | ENGINEERING | REVIEW | Approved | |
| 12/11/2012 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 12/12/2012 | MARTIN BROWN | FIRE | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/17/2012 | SHANAE POWELL | OUT TO CUSTOMER | Completed |