Permit Number: T12CM07808
Parcel: 10511061F

Address:
4530 N ORACLE RD

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T12CM07808
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/25/2013 GERRY KOZIOL WWM REVIEW Passed
12/11/2012 STEVE SHIELDS ZONING REVIEW Approved
12/11/2012 ROBERT SHERRY WATER REVIEW Approved
12/11/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T12CM07808

1. Provide a discription of new work,provide circuit identification, panel identification,a panel schedule with loads and loaction ,and fixture loads.

Ray T Majuta
Elect Plan Review
PDSD, C of Tucson
12/11/2012
Ray.Majuta@tucsonaz.gov
12/11/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
12/11/2012 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET A200; DEMOLITION FLOOR PLAN: THERE ARE 13 DEMOLITION KEYNOTES LISTED, BUT ONLY 5 DIFFERENT KEYNOTES SHOWN ON THE PLAN. CLARIFY.
2. SHEET A200; FLOOR PLAN LEVEL 1: THERE IS A JCP MERCHANDISE WALL DETAIL AT THE INTERIOR WALL NOTED AS 91. CLARIFY.
3. SHEET A200; FLOOR PLAN LEVEL 1: THERE ARE SEVERAL KEYNOTES MISSING ON THE PLAN. CLARIFY.
4. GENERAL: DARKEN THE DRAWINGS SO PLOTS WILL BE READABLE.
5. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
12/11/2012 PAUL MACHADO ENGINEERING REVIEW Approved
12/11/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
12/11/2012 ERIC NEWCOMB ADA REVIEW Passed
12/11/2012 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
12/12/2012 MARTIN BROWN FIRE REVIEW Approved