Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T12CM07808
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/25/2013 | GERRY KOZIOL | WWM | REVIEW | Passed | |
| 12/11/2012 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 12/11/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 12/11/2012 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 12/11/2012 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 12/11/2012 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
| 12/11/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 12/11/2012 | PAUL MACHADO | ENGINEERING | REVIEW | Approved | |
| 12/11/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T12CM07808 1. Provide a discription of new work,provide circuit identification, panel identification,a panel schedule with loads and loaction ,and fixture loads. Ray T Majuta Elect Plan Review PDSD, C of Tucson 12/11/2012 Ray.Majuta@tucsonaz.gov |
| 12/11/2012 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET A200; DEMOLITION FLOOR PLAN: THERE ARE 13 DEMOLITION KEYNOTES LISTED, BUT ONLY 5 DIFFERENT KEYNOTES SHOWN ON THE PLAN. CLARIFY. 2. SHEET A200; FLOOR PLAN LEVEL 1: THERE IS A JCP MERCHANDISE WALL DETAIL AT THE INTERIOR WALL NOTED AS 91. CLARIFY. 3. SHEET A200; FLOOR PLAN LEVEL 1: THERE ARE SEVERAL KEYNOTES MISSING ON THE PLAN. CLARIFY. 4. GENERAL: DARKEN THE DRAWINGS SO PLOTS WILL BE READABLE. 5. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 12/12/2012 | MARTIN BROWN | FIRE | REVIEW | Approved |