Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T12CM07800
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/16/2013 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T12CM07800 5975 E Speedway Bl 1. Last review of 6/24/2013 (item #4) requested new service design was to have a new grounding system per 250.24. 2. Sheet 3 of 17, the 4 3/0 kcmil conductors from the new CT Can to the PV 250 amp fused Disconnect should be 4 250 kcmil, same as secondary side of disconnect. Please change on all sheets as required. Ray T Majuta Electrical Plan Review PDSD, C of Tucson 7/16/2013 Ray.Majuta@tucsonaz.gov 520-837-4988 |
| 07/18/2013 | SPOWELL1 | ZONING | REVIEW | Needs Review |