Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T12CM07790
Parcel: 10511043B

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T12CM07790
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/10/2012 STEVE SHIELDS ZONING REVIEW Approved
12/11/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Clarify the design of the outside air intakes for the fan coil units. Reference: Section 106.3.1, IMC 2006.
2. Provide calculations to determine the amount of outside air to be supplied to the fan coils. Reference: section 403.3, IMC 2006.
12/11/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
12/11/2012 ROBERT SHERRY WATER REVIEW Approved
12/11/2012 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
12/11/2012 LAITH ALSHAMI ENGINEERING REVIEW Approved
12/11/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Provide an upper terminal cleanout for the new sink. Reference: Section 707.4, UPC 2006.
12/11/2012 KEN BROUILLETTE FIRE REVIEW Approved
12/11/2012 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
12/11/2012 ERIC NEWCOMB ADA REVIEW Passed
12/13/2012 FRODRIG2 WWM REVIEW Approved