Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T12CM07790
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
12/10/2012 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
12/11/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Clarify the design of the outside air intakes for the fan coil units. Reference: Section 106.3.1, IMC 2006. 2. Provide calculations to determine the amount of outside air to be supplied to the fan coils. Reference: section 403.3, IMC 2006. |
12/11/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
12/11/2012 | ROBERT SHERRY | WATER | REVIEW | Approved | |
12/11/2012 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
12/11/2012 | LAITH ALSHAMI | ENGINEERING | REVIEW | Approved | |
12/11/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Provide an upper terminal cleanout for the new sink. Reference: Section 707.4, UPC 2006. |
12/11/2012 | KEN BROUILLETTE | FIRE | REVIEW | Approved | |
12/11/2012 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
12/11/2012 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
12/13/2012 | FRODRIG2 | WWM | REVIEW | Approved |