Permit Number: T12CM07753
Parcel: 107020290

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T12CM07753
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/07/2013 GERRY KOZIOL WWM REVIEW Approved
01/07/2013 PAUL MACHADO ENGINEERING REVIEW Approved
01/08/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
12/13/2012 MARTIN BROWN FIRE REVIEW Approv-Cond PROVIDE KEY BOXES AND HMIS BY FINAL
12/17/2012 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied SHEET T1.0
1. The governing building code adopted for the City of Tucson effective 10 July 2007, is the 2006 IBC which includes accessibility requirements as per Chapter 11 and the ICC A117.1, 2003 Edition.
a. Please delete all references to the Arizonans with Disibility Act and Implementation Rules.
SHEETS A6.0 AND A7.0
2. As per comment 1 above, delete all references to ADA and insure that all accessibility details and requirements are as per the 2006 IBC, Chapter 11 and ICC A117.1, 2003 Edition.
3. At details 4 and 5/A6.0, the accessible counter height should be 36" a.f.f. as required by ICC A117.1, Section 904. Please reconcile and resubmit.
4. Please show the water closet clearance as required by ICC A117.1, Section 604.3 at both details 1 and 2.
5. Please detail the water dispensers and indicate the correct mounting heights for both spouts as required by Chapter 11, Section 1109.5 and ICC A117.1, Section 602.4.
SHEET S1.1
6. Please provide certifications for the special inspectors required.
7. Reference detail 204/S4.1 at the canopy framing plan does not exist.
8. Please provide a written response to all comments.
END OF REVIEW
12/20/2012 DAVID RIVERA ZONING REVIEW Denied Zoning has reviewed the building plans but cannot approve them until the Development Package Site plan is approved and all comments by other reviewers have been addressed. If changes are made to teh building plans that affect zoning requirements, additional review comments will be forthcoming.
12/26/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Revise the size of the condensate drains in accordance with Section 307.2.1, IMC 2006, as amended by the City of Tucson.
2. The occupant load used to calculate the required ventilation is not necessarily the same as the occupant load used for calculating exiting requirements (see the conference room). The occupant load used for calculating the minimum required ventilation is to be based on Table 403.3, IMC 2006 or an approved engineering analysis of the specific occupancy type. Reference: Section 403.3, IMC 2006.
3. Provide calculations to show that each of the common ventilation systems (RTU-1 and RTU-2) is sized in accordance with Section 403.3.2, IMC 2006.
4. Verify that a manual emergency shutoff control for the ventilation of the cylinder storage area is in place per Item (4), Section 502.8.1.1, IMC 2006.
12/26/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide a design for mounting the water heater shelf along with structural calculations to show that the water heater is safely supported from the building structure. Reference: Sections 310.0 and 314.5, UPC 2006.
2. Provide a vacuum relief for the storage-type water heater located above the fixture outlets. Reference: Section 608.7, UPC 2006.
3. Provide a vent for each fixture trap (e.g. floor drains). Reference: Sections 901.0 and 910.1, UPC 2006.
4. Verify that the size of the trap and trap arm assembly for each lavatory complies with the requirements of Section 1003.3, UPC 2006 (i.e. the maximum size for the trap and trap arm assembly is 1-1/2").
12/26/2012 ROBERT SHERRY WATER REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
01/18/2013 CPIERCE1 REJECT SHELF Completed