Permit Number: T12CM07745
Parcel: 104092230

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T12CM07745
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/06/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved T12CM07745

1. Panel locations for existing H and L in same room not shown clearly, where will the new Lighting Contactor go on same wall ? What about required clearances ?
2. Sheet E1.0, circuits L-39 and 40 used, panel schedule shows as spares.
3.Sheet E-4. all text to be minimun 3/32"(Commercial Submittal Requirement).

Ray T Majuta
Elect Plan Review
PDSD, City of Tucson
2/06/2013
Ray.Majuta@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
02/07/2013 FERNE RODRIGUEZ OUT TO CUSTOMER Completed
02/07/2013 CPIERCE1 REJECT SHELF Completed