Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T12CM07745
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/06/2013 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T12CM07745 1. Panel locations for existing H and L in same room not shown clearly, where will the new Lighting Contactor go on same wall ? What about required clearances ? 2. Sheet E1.0, circuits L-39 and 40 used, panel schedule shows as spares. 3.Sheet E-4. all text to be minimun 3/32"(Commercial Submittal Requirement). Ray T Majuta Elect Plan Review PDSD, City of Tucson 2/06/2013 Ray.Majuta@tucsonaz.gov |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/07/2013 | FERNE RODRIGUEZ | OUT TO CUSTOMER | Completed |
| 02/07/2013 | CPIERCE1 | REJECT SHELF | Completed |