Permit Number: T12CM07745
Parcel: 104092230

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T12CM07745
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/08/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Show the location of the gas meter on the plans. Reference: Section 106.3.1, IFGC 2012.
2. Provide a complete diagram of the natural gas distribution system showing the all of the loads, developed lengths, and the layout of the distribution piping on a plan view of the building. Reference: Section 106.3.1, IFGC 2012.
3. Provide gas pipe sizing calculations demonstrating conformance to Section 402.1 and 402.3, IFGC 2012.
4. Show how the temperature of the hot water supply to the public lavatories is controlled. Reference: Section 416.5, IPC 2012 and Section C404.3, IECC 2012.
5. Clarify the termination points for the T&P relief piping and for the drain for the pan under the water heater. The electric water heater detail does not appear to be coordinated with the plumbing plan with regard to the location of the water heater as compare to the location of the mop sink. In addition, an indirect waste receptor (e.g. a hub drain) shall not be installed in a restroom. Reference: Sections 106.3.1, 504.6, 504.7.2 and 802.3, IPC 2012.
6. Provide a vacuum relief valve for the specified bottom-fed storage-type water heater (A. O. Smith DEL-10). Reference: Section 504.2, IPC 2012.
7. Revise the electric water heater detail to show the installation of the thermal expansion tank. Reference: Section 607.3, IPC 2012.
8. Provide cleanouts for all horizontal drains; the cleanouts shall be sized per Section 708.7, IPC 2012 and shall open to allow cleaning in the direction of flow. Reference: Sections 708.3.1 and 708.5, IPC 2012.
9. Provide protection of the trap seals for all floor drains subject to infrequent use. Reference: Section 1002.4, IPC 2012.
01/15/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T12CM07745
4055 N Oracle Rd

1. Identify location of Main Service on plan, also Panels A and B .
2. Provide a drawing of the main service showing ampacity, size of conduits and conductors involved. Indicate if system grounded properly.
3. Identify the AIC value at the service and how it is brought down to a value of 10 KAIC as shown on panels A and B.
4. Provide existing load on the Main Service ( describe how obtained) and provide a total load on service including this space load, ( adding almoust 300 amps this space)
5. The following circuits are listed as lighting loads on panel schedule however supplying different loads.(B-29,31,33,35 and 37)
6. The following circuits are for receptacles not track lighting as shown on panel schedule (B-27)
7. Circuit B-30 is used for Security Equipment not microwave as shown on Panel Schedule.
8. Circuit B-20 for EWH not shown on plan.
9. Show location of Relay Panel (Lighting)

Ray T Majuta
Electrical Plan Review
PDSD, C of Tuc
1/15/2013