Permit Number: T12CM07744
Parcel: 11706245C

Address:
202 E 12TH ST

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T12CM07744
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/16/2013 MARTIN BROWN FIRE REVIEW Approved
01/28/2013 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied RESUBMITTAL COMMENTS ARE IN ALL CAPS

STRUCTURAL DRAWINGS
1. Please provide structural calculations for the following:
a. OK

b. Fan coil unit suspension details and calculations.
NON-RESPONSIVE, NO CLACULATIONS PROVIDED


2. OK

SHEET I2.1
3. The reception bar is not accessible as required by ICC A117.1, 2003 Edition, section 904 which requires a section no higher than 3' a.f.f.
ON DETAIL 5/i21, A HAND WRITTEN NOTE REFERENCING TO SHEET "A-1" FOR REQUIRED MOUNTING HEIGHT PER CODE FOR THE ACCESSIBLE RECEPTION COUNTER IS NOT VALID. NO MOUNTING HEIGHTS SHOWN ON SHEET "A-1".

SHEET A1 AND A1.1
4. Remove all references to ADAAG and refer to the accessible governing code 2006 IBC, Chapter 11 and ICC A117.1, 2003 Edition.
NOTE 10.1, SHEET A1 IS NOT CORRECTED.

a. OK

SHEET A1.2
5. 5. At detail 7, please revise the following:
a. OK
b. OK
c. Provide a ramp handrail elevation including the bottom horizontal bar at a maximum of 4" a.f.f. as per ICC A117.1, Section 405.9.
PLEASE REFERENCE THE DETAIL 3/A3.1 FROM THE RAMP PLAN.
END OF REVIEW
01/29/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
01/31/2013 CPIERCE1 REJECT SHELF Completed
01/29/2013 CPIERCE1 APPROVAL SHELF Completed