Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T12CM07744
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/04/2013 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 01/08/2013 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 12/13/2012 | MARTIN BROWN | FIRE | REVIEW | Denied | Sheet TS1 states "Wet stand pipes - N/A". Per 2006 International Fire Code, section 905.11, wet stand pipes are required. Additionally, the 2012 fire code will require fire extinguishers in new and existing R-2 occupancies. Refer to section 906. Please add note to cover sheet. Add note indicating fire department approved lock box will be installed. |
| 12/18/2012 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | STRUCTURAL DRAWINGS 1. Please provide structural calculations for the following: a. All new structural foundation and steel framing plans and details b. Fan coil unit suspension details and calculations 2. Please provide certification for special inspectors as specified. SHEET I2.1 3. The reception bar is not accessible as required by ICC A117.1, 2003 Edition, section 904 which requires a section no higher than 3' a.f.f. SHEET A1 AND A1.1 4. Remove all references to ADAAG and refer to the accessible governing code 2006 IBC, Chapter 11 and ICC A117.1, 2003 Edition. a. Insure that all accessible design elements shown on the drawings comply with this governing code. SHEET A1.2 5. At detail 7, please revise the following: a. Please show all required accessible dimensions. A minimum of 20.4' of run is required to maintain a 1:12 slope of the ramp. The ramp runs are not dimensioned. b. A 5' square landing is required at the 90 degree turn as per ICC A177.1, Sections 405.7.4 and 305.3. c. Provide a ramp handrail elevation including the bottom horizontal bar at a maximum of 4" a.f.f. as per ICC A117.1, Section 405.9. END OF REVIEW |
| 12/26/2012 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 12/26/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 12/27/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Clarify the scale of the mechanical plan on M1.1 and indicate the location of the match line for the partial mechanical plan shown on 2/M1.2. 2. Clarify the abbreviations "HCWS" and "HCWR". |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/15/2013 | CPIERCE1 | OUT TO CUSTOMER | Completed |
| 01/15/2013 | CPIERCE1 | REJECT SHELF | Completed |