Permit Number: T12CM07744
Parcel: 11706245C

Address:
202 E 12TH ST

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T12CM07744
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/04/2013 GERRY KOZIOL WWM REVIEW Approved
01/08/2013 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Approved
12/13/2012 MARTIN BROWN FIRE REVIEW Denied Sheet TS1 states "Wet stand pipes - N/A". Per 2006 International Fire Code, section 905.11, wet stand pipes are required.
Additionally, the 2012 fire code will require fire extinguishers in new and existing R-2 occupancies. Refer to section 906. Please add note to cover sheet.
Add note indicating fire department approved lock box will be installed.
12/18/2012 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied STRUCTURAL DRAWINGS
1. Please provide structural calculations for the following:
a. All new structural foundation and steel framing plans and details
b. Fan coil unit suspension details and calculations
2. Please provide certification for special inspectors as specified.
SHEET I2.1
3. The reception bar is not accessible as required by ICC A117.1, 2003 Edition, section 904 which requires a section no higher than 3' a.f.f.
SHEET A1 AND A1.1
4. Remove all references to ADAAG and refer to the accessible governing code 2006 IBC, Chapter 11 and ICC A117.1, 2003 Edition.
a. Insure that all accessible design elements shown on the drawings comply with this governing code.
SHEET A1.2
5. At detail 7, please revise the following:
a. Please show all required accessible dimensions. A minimum of 20.4' of run is required to maintain a 1:12 slope of the ramp. The ramp runs are not dimensioned.
b. A 5' square landing is required at the 90 degree turn as per ICC A177.1, Sections 405.7.4 and 305.3.
c. Provide a ramp handrail elevation including the bottom horizontal bar at a maximum of 4" a.f.f. as per ICC A117.1, Section 405.9.
END OF REVIEW
12/26/2012 ROBERT SHERRY WATER REVIEW Approved
12/26/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
12/27/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Clarify the scale of the mechanical plan on M1.1 and indicate the location of the match line for the partial mechanical plan shown on 2/M1.2.
2. Clarify the abbreviations "HCWS" and "HCWR".

Final Status

Task End Date Reviewer's Name Type of Review Description
01/15/2013 CPIERCE1 OUT TO CUSTOMER Completed
01/15/2013 CPIERCE1 REJECT SHELF Completed