Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T12CM07735
Parcel: 10511061R

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T12CM07735
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/06/2012 TERRY STEVENS ZONING REVIEW Approved
12/06/2012 LOREN MAKUS ENGINEERING REVIEW Approved
12/07/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T12CM07735
T Mobile

1. Need to provide loaction of MSB and show on plan.
2. Is meter,60 amp switch, transformer and panel new,please indicate on plan,if new indicate AIC at 60 amp sw and Pnl H.
3.The B fixtures not on Lighting Compliance Report ?

Ray T Majuta
PDSD, C of Tuc
Elect Pln Review
12/07/2012
Ray.Majuta@tucsonaz.gov
12/07/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
12/07/2012 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET A-0; REFERENCE CODES: REVISE THE REFERENCE OF THE ACCESSIBILITY CODE FROM THE ADAAG TO THE ICC/ANSI A117.1-2003.
2. SHEET A-6; ELEVATIONS G1 AND G4: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE THE DIMENSIONS.
3. SHEET A-6; ELEVATION A1(B): PROVIDE THE VERTICAL GRAB BAR PER ICC/ANSI A117.1-2003 FIGURE 604.5.1.
4. SHEET A-8; DETAIL D1: PROVIDE THE VERTICAL GRAB BAR PER ICC/ANSI A117.1-2003 FIGURE 604.5.1.
5. SHEETS A-12 THROUGH A-15: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE THE NOTES.
6. GENERAL: PROVIDE A DETAIL FOR THE BRACING OF NEW INTERIOR WALLS THAT STOP JUST ABOVE THE CEILING. THESE WALLS MUST MEET THE REQUIREMENTS OF THE IBC SECTION 1607.13 FOR LATERAL STABILITY. INCLUDE IN THE DETAIL BRACING SIZE AND SPACING, AND THE CONNECTION OF THE BRACING AT THE TOP OF THE PARTITION WALL, AND TO THE EXISTING STRUCTURE ABOVE.
7. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
12/07/2012 ROBERT SHERRY WATER REVIEW Approved
12/07/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide the listing information for the proposed temperature mixing valve. Reference: Sections 301.1.1, 401.1, and 413.1UPC 2006., UPC 2006; and Section 504.3, IECC 2006.
2. Provide a vacuum relief for the storage-type water heater located above the fixture outlets. Reference: Section 608.7, UPC 2006.
12/07/2012 ERIC NEWCOMB ADA REVIEW Passed
12/07/2012 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
12/10/2012 KEN BROUILLETTE FIRE REVIEW Approved
12/14/2012 GERRY KOZIOL WWM REVIEW Approved