Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T12CM07729
Parcel: 14026045A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T12CM07729
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/06/2012 MICHAEL ST. PAUL ZONING REVIEW Approved
12/06/2012 PAUL MACHADO ENGINEERING REVIEW Approved
12/06/2012 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Approved
12/06/2012 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
12/06/2012 ERIC NEWCOMB ADA REVIEW Passed
12/07/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide structural calculations to verify that the existing roof is capable of supporting the additional dead load due to the installation of the roof top units and the evaporative cooler. Reference: Section 302.1, IMC 2006.
2. Revise the sequence of operation for the restroom exhaust fan so that all of the air supplied to the restrooms will be exhausted. Reference: Section 403.2.1 (4), IMC 2006.
12/07/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The size of a wet vent shall be a minimum of one pipe size greater than that required for the drain of the upper fixture. Reference: Section 908.2, UPC 2006.
2. Provide water service and a drain for the new evaporative cooler.
12/07/2012 ROBERT SHERRY WATER REVIEW Approved
12/07/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
12/10/2012 KEN BROUILLETTE FIRE REVIEW Approv-Cond High piled storage is not allowed unless compliance with Chapter 23 of the 2006 IFC. Sprinkler monitoring is required. The fire sprinkler system shall be designed for the type of storage and NFPA 13. Key box is required if not already on fire sprinkler riser room.
12/14/2012 GERRY KOZIOL WWM REVIEW Approved