Permit Number: T12CM07724
Parcel: 11012094A

Address:
5301 E GRANT RD

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T12CM07724
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/12/2012 GERRY KOZIOL WWM REVIEW Passed
12/17/2012 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
12/18/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T12CM07724
5301 E Grant Rd
Corridor Remodel

1. Identify circuits and panels being used to refeed power and lighting.
2.Show revised panel loads and locations on plan.

Ray T Majuta
Elect Plan Review
PDSD, C of Tucson
12/18/2012
Ray.Majuta@tucsonaz.gov
12/21/2012 ROBERT SHERRY WATER REVIEW Approved
12/21/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
12/21/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
12/24/2012 KEN BROUILLETTE FIRE REVIEW Approved