Permit Number: T12CM07608
Parcel: 12606204A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T12CM07608
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/13/2012 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Denied 1) Buildings of type II and III require non-combustible materials in exterior wall construction. Clarify how 2x6 framing and OSB sheathing at new canopy walls and soffit meet this requirement.

1a) Provide details for attachment of soffit framing at new canopy.

1b) Structural calculations for canopy do not provide necessary information to indicate whether sheathing meets live + dead load requirements (provided table is not for specified sheathing and is incomplete for purposes of review).

2) Detail references for walls PP A1 do not correctly reflect actual details on PP A4.2.

3) Not a required correction, but please review wall details on PP A4.2, particularly details for wall type 4B. Bracing and firestop requirements may want to be revised.

4) Caution: plans meet code requirements but detail 1 PP A4.2 indicates an 8 gauge hanger wire..this is not an industry standard and may be a problem in the field. 9 gauge is readily available standard.
12/13/2012 LEERAY HANLY PLUMBING-COMMERCIAL REVIEW Approved
12/17/2012 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Approved
12/17/2012 LEERAY HANLY MECHANICAL-COMMERCIAL REVIEW Approved
12/19/2012 GERRY KOZIOL WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
12/24/2012 CPIERCE1 REJECT SHELF Completed