Permit Number: T12CM07583
Parcel: 105102430

Review Status: Completed

Review Details: OTHER

Permit Number - T12CM07583
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/14/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied 1. The new space merter is single phase, not stated on plan if 600 amp service is also single phase, I assume the 600 a service is 3 phase, which phases will new service tap into ?
2. Will new service be 6 th main on the 600 amp service ?

Ray Majuta
elect pln ck
12/14/12
12/14/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved