Permit Number: T12CM07583
Parcel: 105102430

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T12CM07583
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/30/2012 MICHAEL ST. PAUL ZONING REVIEW Approved
11/30/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide a mechanical plan. "Design /Build" is not acceptable.
11/30/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T12CM07593

1. Provide total load on main service then add this space to vewrify sufficient.
2. Show location of main service .

Ray T Majuta
Elect Pln Review
11/30/2012
11/30/2012 ROBERT SHERRY WATER REVIEW Approved
11/30/2012 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
11/30/2012 LAITH ALSHAMI ENGINEERING REVIEW Approved
11/30/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
11/30/2012 MARTIN BROWN FIRE REVIEW Approved
11/30/2012 RONALD BROWN COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
11/30/2012 RONALD BROWN ADA REVIEW Passed
12/14/2012 GERRY KOZIOL WWM REVIEW Passed