Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T12CM07541
Parcel: 115073010

Address:
22 W DRACHMAN ST

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T12CM07541
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/04/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
02/04/2013 LAITH ALSHAMI ENGINEERING REVIEW Approved
02/04/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
02/04/2013 ROBERT SHERRY WATER REVIEW Approved
02/04/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the waste and vent isometric to coordinate with the plumbing plan.
2. Prep sinks shall be indirectly wasted.
3. Revise the grease trap piping diagram to show the sanitizing sink being indiretly wasted to a trapped and vented indirect waste receptor.
4. Provide a floor drain for the new restroom.
5. Provide an expansion tank for the water heater.
02/06/2013 SPOWELL1 WWM REVIEW Needs Review