Review Details: COMMERCIAL - TI

Permit Number - T12CM07541
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/11/2013 MARTIN BROWN FIRE REVIEW Approved
01/11/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
01/11/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T12CM07541
22 W Drachman

1. Provide the size of the overhead conductors in the riser, cannot be overloaded.
2. How was the total 113 amp load for the service obtained, and has new load been added to this ?
3. Size the conductors fron the wireway to the 200 amp disconnect.
4. Size the fuse in the 200 amp disconnect.
5. The conductors from the disconnect to panel A are only 100 amp ?
6. All kitchen receptacles per 2005 NEC 210.8.A.6 are requirwd to be GFI protected.
7. Tie Exit Lights in a circuit, indicate unswitched.
8. Change F5 to F6 type fixtures on plan.
9. Indicate on plan the voltage and phase type of service.

Ray T Majuta
PDSD, C of Tuc
Elect Plan Review
1/11/2013
01/11/2013 ROBERT SHERRY WATER REVIEW Denied Verify size and location of the backflow preventer for the water service.
01/11/2013 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
01/11/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Clarify which fixtures are new and which are existing.
2. Provide riser diagrams for the water and the waste & vent systems.
3. Show how the water temperature for the new lavatories will be limited to 110 degrees Fahrenheit.
4. Provide specifications for the grease intercepter and show how it will be installed.
5. Provide the pipe size, gas input (BTUH) and developed pipe lengths for each gas-fired appliance.
01/11/2013 ERIC NEWCOMB ADA REVIEW Passed
01/11/2013 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
02/04/2013 FRODRIG2 WWM REVIEW Needs Review
02/04/2013 FRODRIG2 ENGINEERING REVIEW Needs Review
11/29/2012 TERRY STEVENS ZONING REVIEW Approved