Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL - TI ALL
Permit Number - T12CM07526
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/14/2013 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. PREVIOUS COMMENT 1; SHEET A1; WALL TYPE LEGEND: THE REFERENCE TO SHEET 4 IS STILL IN THE VERBIAGE FOR WALL TYPE F. REMOVE THAT VERBIAGE, AND REPLACE THE REFERENCE FROM SHEET 4 TO DETAIL 5/A3. 2. PREVIOUS COMMENT 2; SHEET A2; REFLECTED CEILING PLAN: THE DETAIL CUT 5/A4 IS STILL ON THE PLAN. REMOVE THAT DETAIL CUT, AND REPLACE IT WITH DETAIL CUT 5/A3. 3. GENERAL: REMOVE ALL ORIGINAL PROJECT SHEETS THAT REQUIRE REVISIONS FROM THE FINAL SET. THIS FINAL DRAWING SET SHOULD CONTAIN ONLY 1 COPY OF EACH DRAWING (X1, A1, A2, A3, P1, P2, M1, E1, E2, AND E3), INDICATING REVISIONS WITH CLOUDS. 4. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. THESE RESPONSES TO NOT HAVE TO BE INCLUDED ON THE PROJECT DRAWINGS. |
| 01/25/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 01/25/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Based on the manufacturer's product information, the proposed pedicure chairs are not equipped with a pump to drain the attached sink. Provide justification for the indirect waste connection of the pedicure sinks. Reference: Section 802.1, IPC 2006. |