Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T12CM07526
Parcel: 12307294C

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T12CM07526
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/14/2013 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. PREVIOUS COMMENT 1; SHEET A1; WALL TYPE LEGEND: THE REFERENCE TO SHEET 4 IS STILL IN THE VERBIAGE FOR WALL TYPE F. REMOVE THAT VERBIAGE, AND REPLACE THE REFERENCE FROM SHEET 4 TO DETAIL 5/A3.
2. PREVIOUS COMMENT 2; SHEET A2; REFLECTED CEILING PLAN: THE DETAIL CUT 5/A4 IS STILL ON THE PLAN. REMOVE THAT DETAIL CUT, AND REPLACE IT WITH DETAIL CUT 5/A3.
3. GENERAL: REMOVE ALL ORIGINAL PROJECT SHEETS THAT REQUIRE REVISIONS FROM THE FINAL SET. THIS FINAL DRAWING SET SHOULD CONTAIN ONLY 1 COPY OF EACH DRAWING (X1, A1, A2, A3, P1, P2, M1, E1, E2, AND E3), INDICATING REVISIONS WITH CLOUDS.
4. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. THESE RESPONSES TO NOT HAVE TO BE INCLUDED ON THE PROJECT DRAWINGS.
01/25/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
01/25/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Based on the manufacturer's product information, the proposed pedicure chairs are not equipped with a pump to drain the attached sink. Provide justification for the indirect waste connection of the pedicure sinks. Reference: Section 802.1, IPC 2006.