Review Date Reviewer's Name Type of Review Description Status Comments
12/05/2012 KEN BROUILLETTE FIRE REVIEW Approved
12/07/2012 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET A1; WALL TYPE LEGEND: A NOTE FOR WALL F INDICATES TO SEE SHEET 4 FOR WALL BRACING. REVISE THE SHEET REFERENCE (NO SHEET 4).
2. SHEET A2; REFLECTED CEILING PLAN: A DETAIL 5/A4 IS CUT AT AN INTERIOR WALL. REVISE THE SHEET REFERENCE (NO SHEET A4).
3. GENERAL: IN ACCORDANCE WITH THE CITY OF TUCSON RECOMMENDATIONS AND THE IBC SECTION 3409.7, PROVIDE UPGRADES OF THE ACCESSIBLE ROUTE, RESTROOM GRAB BARS, OR OTHER ACCESSIBILITY IMPROVEMENTS (UP TO 20% OF THE PROJECT COST). NOTE THESE IMPROVEMENTS ON THE PLAN.
4. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
12/17/2012 GERRY KOZIOL WWM REVIEW Approved
12/17/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide material standards for all plumbing fixtures being provided by others. Reference: Section 303.4, IPC 2006.
2. Provide the listing information for the pedicure units. If the listing does not include integral backflow protection for the pull-out sprayer, revise the design to provide reduced pressure backflow preventers for the hot and cold water supplies. Reference: Sections 303.4 and 608.13, IPC 2006.
3. Provide structural calculations and details to verify that the proposed water heater will be safely supported by the building structure. Reference: Sections 106.3.1 and 301.2, IPC 2006.
12/17/2012 ROBERT SHERRY WATER REVIEW Approved
12/17/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Revise the exhaust system to capture the contaminants and odors from the nail drying station. Reference: footnote I, Table 403.3, IMC 2006.
12/20/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved