Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T12CM07490
Parcel: 11305076A

Address:
3500 N CHERRY AV

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T12CM07490
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/05/2012 KEN BROUILLETTE FIRE REVIEW Approv-Cond THIS SCHOOL IS REQUIRED TO BE REVIEWED AND APPROVED BY THE STATE FIRE MARSHAL'S OFFICE. NO REVIEW BY TFD WILL OCCUR AT THIS TIME.
12/10/2012 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. At detail 2/A7.0, as required by ICC A117.1, Section 604.3, the lavatory may not encroach upon the clearance required for the water closet. Please reconfigure the toilet room layout and resubmit.
END OF REVIEW
12/14/2012 ROBERT SHERRY WATER REVIEW Approved
12/14/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Restrooms 122 and 124 have hot (tempered?) water supplied to the lavatories; what is the source of the hot water? Reference: Section 607.2, IPC 2006.
2. Verify that the indirect waste pipe from P34 is trapped. Reference: Section 802.2, IPC 2006.
3. All dry vents located within the building (e.g. the kitchen, room 118: the southern combination drain and vent system and the portion of the vent for the grease interceptor) shall rise vertically at least 6-inches above the flood level rim of the highest fixture being vented prior to offsetting horizontally. Reference: Section 905.4, IPC 2006.
4. Detail 6/P3.1 calls for the water heater support to be mounted in an "approved manner"; provide structural details describing how the support is to be attached to the building structure.
5. Show that the combination drain and vent systems in room 118 are adequately vented (i.e. do the vent sizes comply with Table 912.3, IPC 2006). Reference: section 912.2.3, IPC 2006.
6. Section 607.1, IPC 2006 requires all nonresidential fixtures used for cleansing to be provided with hot water. What is the purpose of the classroom sinks?
7. Modify length of the trap arm for the floor drain located in room 612 to conform to Table 906.1, IPC 2006. Reference: Section 906.1, IPC 2006.
8. Provide a trap seal primer valve for the floor drains located in rooms 612 and 614. Reference: Section 1002.4, IPC 2006.
9. An approved 2-way cleanout fitting is a single fitting, not a field-assembled group of individual fittings as shown in detail 2/C3.0. Reference: Sections 708.3.5 and 708.5, IPC 2006.
10. Keynote 8 on sheet C3.0 calls for a backwater valve for building 6. Provide the first floor elevations of the other buildings and the rim elevation of the next upstream manhole in the public sewer. Reference: Section 715.1, IPC 2006, as amended by the City of Tucson.
12/17/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
12/17/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide information on the sequence of operation for the restroom exhaust fans, EF-1 through EF-4 and EF-7 through EF-15. Verify that all of the air supplied to the restrooms will be exhausted. Reference: Section 403.2.1 (4), IMC 2006.
2. Section 507.2.2, IMC 2006, exception 3, allows the installation of a "single light-duty electric convection, bread, retherm, or microwave oven" without the requirement of installing a Type II hood. The food service drawings indicate that the cook line has two steamers (6.0kW each), two "cook & hold" ovens (5.0 kW each), and a thermalizer cabinet (7.0 kW). Provide justification for not installing a type II hood over all of these appliances and show that the air conditioning system can accommodate the heat generated by them.
3. Detail 3/P3.1 indicates that no condensate trap will be provided for the ductless air conditioners. Provide information from the manufacturer that shows that this is an approved installation method. Reference: Section 307.2.4, IMC 2006.
4. Clarify how the return air for AC-10 will be balanced.
12/27/2012 GERRY KOZIOL WWM REVIEW Denied 1: HOLOWAY ELEMENTARY SCHOOL - DP12-0222 - ADDED 115FU'S (163 WATER FU'S PER PLUMBING FIXTURE SCHEDULE P2.1)
2: CONNECTING TO EXISTING WATER METER PER DRAWING SCHEDULE P2.1 & EXISTING ON-SITE PRIVATE SEWER PER DRAWING C3.0 PER PERMITS #18649 DATED 09/16/85 AND PERMIT #35981 DATED 08/02/93
3: NEED WASTEWATER CAPACITY REVIEW - PCRWRD/3RD FLOOR/KURT STEMM 740-6534
4: NEED PCRWRD/INDUSTRIAL WASTEWATER CONTROL (IWC) REVIEW OF 500 GALLON GREASE INTERCEPTOR - "RUSTY" 724-6200 - 3035 W EL CAMINO DEL CERRO -
GK 12/27/12

Final Status

Task End Date Reviewer's Name Type of Review Description
01/18/2013 CPIERCE1 REJECT SHELF Completed