Permit Number: T12CM07485
Parcel: 12809006B

Address:
5443 E 22ND ST

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T12CM07485
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/27/2012 TERRY STEVENS ZONING REVIEW Approved
11/27/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
11/27/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
11/27/2012 ROBERT SHERRY WATER REVIEW Approved
11/27/2012 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
11/27/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The flow control device for a hydromechanical grease interceptor shall be installed in a location that is readily accessible and visible. Reference: Section 1014.2.1, UPC 2006.
2. Provide an indirect connection for the sanitizing compartment of the 3-compartment sink, with a direct waste connection for the wash and rinse sections only. Reference: Sections 304.0, 704.3, and 801.2.3, UPC 2006.
3. Modify trap arm lengths for the lavatories to conform to Table 10-1, UPC 2006. Reference: Section 1002.2, UPC 2006.
4. Show how the temperature of the hot water supply to the public lavatories is controlled. Reference: Section 413.1, UPC 2006 and Section 504.3, IECC 2006.
5. Provide a vacuum relief for a storage-type water heater located above any fixture outlets. Reference: Section 608.7, UPC 2006.
11/27/2012 KEN BROUILLETTE FIRE REVIEW Approved
11/27/2012 RONALD BROWN COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
11/27/2012 RONALD BROWN ADA REVIEW Passed
12/10/2012 SPOWELL1 WWM REVIEW Needs Review
12/10/2012 SPOWELL1 ENGINEERING REVIEW Needs Review