Review Date Reviewer's Name Type of Review Description Status Comments
12/18/2012 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS
Date: 12-19-2012
Activity: T12CM07468
Address: 2437 S Kevin Dr
Applicant: John Riggs

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review includes architectural, electrical, plumbing, mechanical, and energy conservation. The purpose of this review is to verify compliance to the 2006 International Residential Code with local amendments. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions, and concerns before permit approval.

SITE PLAN:
1. Include the location of the barrier between the house and the pool per IRC amendment

PLUMBING PLAN:
2. Provide a water fixture unit schedule for the entire property (including existing) P2903.6.
3. Tucson Water Department limits 5/8" water meters to a maximum of 11 IRC fixture units or 15 gallons per minute. Specify a ¾" water meter upgrade.

INTERNATIONAL ENERGY CONSERVATION CODE:
4. Specify the "R" value of the insulation greater to or equal to the prescriptive requirements or submit justified analysis. The simplified prescribed energy values for ceilings = R-30, N1102.1.

If you have any questions please contact:
Clayton Trevillyan
520.837.4913
Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
12/28/2012 CPIERCE1 REJECT SHELF Completed