Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T12CM07467
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/22/2013 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 03/01/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | There are two errors in the envelope energy code calculations, one major and one minor. First, you have used the Town of Pima as the basis for the calculations; the town is located in Graham County and has a different climate than the City of Tucson. You can find Pima County<4,000 feet in the drop-down menu under "Code" on COMcheck. Using your input values, COMcheck shows that the addition fails by 2% in Pima County. Second, in this climate zone, the slab does not require any insulation (you can ignore the slab if you wish) but the input value for the slab is the slab perimeter, not the slab area. Your window has a high SHGF; reducing the value to 0.60 will result in a passing score. [Original comment: Provide energy code compliance calculations for the additions to the building envelope; use the climate zone for Pima County < 4,000 feet. Provide sufficient detail on the drawings to evaluate the energy compliance of the additions to the building envelope. The information shall, as a minimum, include U-factors of the envelope systems and fenestration components, along with the R-values of the insulation and the SHGC for the fenestration. Reference: Sections 101.4, 101.4.3, and 104.2, International Energy Conservation Code 2006.] |