Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T12CM07467
Parcel: 12801001B

Address:
170 S WILMOT RD

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T12CM07467
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/29/2012 KEN BROUILLETTE FIRE REVIEW Approved
12/06/2012 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. Please provide structural calculations for the project.
2. Please provide certification of special inspectors as required by structural engineer. and the 2006 IBC, Section 1704.
END OF REVIEW
12/12/2012 ROBERT SHERRY WATER REVIEW Approved
12/12/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
12/12/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide energy code compliance calculations for the additions to the building envelope; use the climate zone for Pima County < 4,000 feet. Provide sufficient detail on the drawings to evaluate the energy compliance of the additions to the building envelope. The information shall, as a minimum, include U-factors of the envelope systems and fenestration components, along with the R-values of the insulation and the SHGC for the fenestration. Reference: Sections 101.4, 101.4.3, and 104.2, International Energy Conservation Code 2006.
2. Provide structural details to show how the fan coil unit is to be connected to the building structure. Reference: Section 302.1, IMC 2006.
3. Clarify the termination of the drain from the auxiliary drain pan for the fan coil. Secondary condensate drains shall discharge to a conspicuous point of disposal and shall not damage any building component. Reference: Section 307.2.3 IMC 2006.
12/18/2012 GERRY KOZIOL WWM REVIEW Approved
12/19/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
02/19/2013 CPIERCE1 REJECT SHELF Completed