Permit Number: T12CM07458
Parcel: 123020700

Address:
2625 E EDISON ST

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T12CM07458
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/25/2013 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Reqs Change PLAN REVIEW COMMENTS
Date: 2-26-13
Activity: T12CM07458
Address: 2625 E Edison
Applicant: Tom Meyer

This letter reflects comments to be addressed. The purpose of this review is to verify compliance to the 2006 International Residential Code with local amendments. In order to facilitate a shorter back check time, we request that you please provide two complete sets of revised plans and calculations, along with a written response to each of the noted items indicating action taken. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions, and concerns before permit approval.

STRUCTURAL / FRAMING PLAN:
1. Provide wall bracing on the proposed utility room in accordance with R602.10.

PLUMBING PLAN:
2. Provide an accurate water fixture unit schedule for the entire property (including existing) P2903.6.
3. Specify the size of the proposed water meter and the diameter of the water supply line from the meter to the service entrance, P2903.7.
4. Specify the maximum developed length of water line from the meter the furthest appliance served, and the lowest available working pressure, P2903.7.
5. Clarify the proposed waste/vent isometric. Will the lavatory trap arm connect at the same height as the shower vent?

MECHANICAL PLAN:
6. Show supply and return air ducts with a minimum R-8 insulation when located outside the thermal envelope, N1103.2.1.
7. Provide Manual J/S/D calculations for the forced air unit in accordance with M1401.3, M1601.1.

ELECTRICAL PLAN:
8. Provide a panel schedule: panel size, circuit numbers, ampacity, and wire sizes, E3404.11, E3706.2.

INTERNATIONAL ENERGY CONSERVATION CODE:
9. Specify prescriptive insulation and fenestration values per Table N1102.1.1/R402.1.1 or submit justified analysis. Simplified prescribed energy values for climate zone 2B: ceilings=R-30 windows=U-0.75, SHGC=0.40.

If you have any questions please contact:
Clayton Trevillyan
520.837.4913
Residential Plan Review