Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T12CM07432
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/03/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 12/04/2012 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | GENERAL 1. Please provide certification of required special inspectors. SHEET A2.0 2. Doors scheduled to have panic hardware are 200, 212, 108C and 109B. What about 104, 118, 119, 108B and 108A? 3. Doors 216A and 216B need to swing out with an occupancy load of 50 or more; 2006 IBC, Section 1008.1.2. a. Doors may not reduce the required access travel width to less than 1/2 as per Section 1005.2. SHEET A4.0 4. The accessible urinal stall must be 3'-0" wide as required by ICC A117.1, Sections 605.3 and 305. 5. Please provide all accessible required dimensions and clearances on all partial floor plans and interior elevations. 6. At details 1, 4 and 8, which urinal is the accessible urinal? Please reconcile. 7. Please change all ADA references to 2006 IBC, Chapter 11 and ICC A117.1. 8. Please show both water dispenser spout heights. END OF REVIEW |
| 12/06/2012 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 12/06/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Show that the back-to-back installation of water closets (detail 2/P1.1; mislabeled "Water Heater Detail") complies with the requirements of Section 706.3, IPC 2006. 2. Show how the revised waste and vent piping on the second floor relates to the waste and vent piping for the first floor. Reference: Section 106.3.1, IPC 2006. 3. Clarify the scope of work for the two sinks located between columns K and L on the first floor. Reference: Section 106.3.1, IPC 2006. 4. Verify the size of the CW supply to the bank of seven flush-valve water closets and one urinal. Based on your calculations and the required minimum flow rate for each fixture, the velocity and pressure drop are excessive. Reference: Sections 604.3 and Table 604.4, footnote c, IPC 2006, as amended by the City of Tucson. |
| 12/06/2012 | KEN BROUILLETTE | FIRE | REVIEW | Denied | same exiting concerns as building-will wait for resubmittal |
| 12/07/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide a design for the exhaust and make-up air systems for the batteries in the UPS room (114). Reference: Sections 501.3 and 502.4, IMC 2006. 2. Revise the schedule for the existing air conditioning units to include the total supply air for each unit. Verify the balancing information (supply and outside air) shown in the AC unit schedules and the ventilation calculations. Reference: Sections 106.3.1 and 403.3.4, IMC 2006. 3. Verify the scheduled information for EF-1. Reference: Section 106.3.1, IMC 2006. |
| 12/10/2012 | GERRY KOZIOL | WWM | REVIEW | Approved |